AIR HANDLER
B6BM, B6EM, & B6VM SERIES
INSTALLATION INSTRUCTIONS
IMPORTANT
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer. This includes being
able to install the product according to strict safety guidelines and instructing the customer on
how to operate and maintain the equipment for the life of the product. Safety should always be
the deciding factor when installing this product and using common sense plays an important
role as well. Pay attention to all safety warnings and any other special notes highlighted in the
manual. Improper installation of the furnace or failure to follow safety warnings could result in
serious injury, death, or property damage.
These instructions are primarily intended to assist qualified individuals experienced in the proper
installation of this appliance. Some local codes require licensed installation/service personnel
for this type of equipment. Please read all instructions carefully before starting the installation.
Return these instructions to the customer’s package for future reference.
DO NOT DESTROY. PLEASE READ CAREFULLY & KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Vista de pagina 0
1 2 3 4 5 6 ... 31 32

Indice de contenidos

Pagina 1 - IMPORTANT

AIR HANDLERB6BM, B6EM, & B6VM SERIESINSTALLATION INSTRUCTIONSIMPORTANTATTENTION INSTALLERS:It is your responsibility to know this product better t

Pagina 2 - TABLE OF CONTENTS

10• Iftheairhandlerislocatedinorabovealivingspacewhere damage may result from condensate overflow, an auxiliary drain pan shall be install

Pagina 3

11ELECTRICAL CONNECTIONS WARNING:ELECTRICAL SHOCK, FIRE OREXPLOSION HAZARDFailure to follow safety warnings exactly could result in serious injury or

Pagina 4

12Refer to the thermostat manufacturer’s instruction sheet for detailed mounting and installation information.• Installthegrommet,whichispacked

Pagina 5

13When electric heat packages with circuit breakers are field-installed, the circuit breaker may be used as a disconnecting means in most applications.

Pagina 6 - AIR HANDLER INSTALLATION

145. Weigh in the proper amount of new (or reclaimed) refrigerant. Refer to the air conditioner or heat pump installation manual for the proper type

Pagina 7 - HORIZONTAL LEFT

15DHUMRRDHUMHUMIDISTATMOTORCONTROL BOARDFigure 10. DHUM Wiring Configuration• Terminal4=Hispeed• Terminal5=Medspeed• Terminal6=Lowspeed4

Pagina 8

16Table 2. Filter SizesCABINET SIZE FILTER SIZEA 12 x 20 x 1B 18 x 20 x 1C 20 x 20 x 1RED LED (AN2) DIAGNOSTICOFF Control Fault (No Power)Flash Blower

Pagina 9

17FIGURES & TABLESFigure 11. B6 Series Physical Dimensions3/4”3/4”3/4”13”1 7/8" K.O.11/8” K.O.(typ.)11/4”15/8”17/8”11/4”3 1/4”2 5/8”11/8” K.O

Pagina 10 - CAUTION:

18HorizontalDrain PanVerticalDrain PanCoilAssemblyMotorMount KitBlowerMotorTransformerCapacitorCircuitBreaker (60A)Heating ElementAssemblyFilterTracks

Pagina 11 - WARNING:

19Airflow DataDRY COIL ESP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80*24KA-CABINETLow 683 647 607 563 515 463 406 345Corrected ESP10.00 0.07 0.19 0.30 0.4

Pagina 12

2TABLE OF CONTENTSIMPORTANT SAFETY INFORMATION ...3REQUIREMENTS & CODES ...3GENERAL INFORMATIO

Pagina 13

20B6EMA-CABINETSWITCH SETTINGS0 = OFF, 1 = ONCOOLING OR HEATING AIRFLOW (CFM)DRY COIL ESP1/5 2/6 3/7 4/8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80 0 0 0 585 55

Pagina 14

21Table 7. B6EM (FSHE) Minimum Heating Airflow Settings (CFM)CABINETNOMINAL ELECTIC HEAT KW5 8 10 15 20 25 30A 800 900 1000 1300 N/A N/A N/AB 900 1000

Pagina 15

22B6VMA-CABINETCOOLING AIRFLOW HEATING AIRFLOWA/B SWITCH SETTING0 = OFF, 1 = ONCOOL SWITCH SETTING0 = OFF, 1 = ONAIRFLOW(CFM)A/B SWITCH SETTING0 = OFF

Pagina 16 - TROUBLESHOOTING

23LED 1BLWDTCBLWDTC_RHEATCOOLEACL 1L 2P2RCGWY3A FuseHEATER P1Figure 13. Single Stage Control BoardCRGY2/YO1W2W1YLLED 1HEATER P1L 2HUMEACP23A FuseP3Fig

Pagina 17 - FIGURES & TABLES

24Figure 15. Fixed Speed Motor Control BoardGREENREDSTATUSNOT USEDTEST PORTBLOWER MOTORRCY1TWINDEHUMW1EXPANSIONPORTCOOLHEATFAN SPEED1 2 345 6 78OFF ON

Pagina 18

25WIRING DIAGRAM(Replaces 7110750)Air Handler LegendField WiringFactory Wiring:Low VoltageHigh Voltage¢711075"¤1009711075ACAP.13521246HEATER PLUG

Pagina 19 - Airflow Data

26WIRING DIAGRAM7110760Air Handler with Fixed Speed High Efficiency MotorLegendField WiringFactory Wiring:Low VoltageHigh Vo ltage¢711076(¤05101224024

Pagina 20

27WIRING DIAGRAM7110770Air Handler with Variable Speed High Efficiency MotorLegendField WiringFactory Wiring:Low VoltageHigh Vo ltage¢711077.¤05101224

Pagina 21

28Table 10. B6BM MCA & MOP DataB6BM MINIMUM CIRCUIT AMPACITY & MAXIMUM OVERCURRENT PROTECTIONCABINET CAPACITYHEAT KITMODELNUMBERH6HK-240 VAC,

Pagina 22

29Table 12. Control Board OperationCONTROL SIGNAL & MODE OPERATION TOTAL KW BOARD ACTIONW1 ONLYEHEATON5 KWstage 1 Heat on instantlyHeat blower on

Pagina 23

3IMPORTANT SAFETY INFORMATIONPlease read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special

Pagina 24

30CONTROL SIGNAL & MODE OPERATION TOTAL KW BOARD ACTIONW1 & W2EHEATON5 KWstage 1 Heat on instantlyHeat blower on aFter 3 seCond delay10 KWstag

Pagina 25 - WIRING DIAGRAM

31Table 12. Control Board Operation - ContinuedCONTROL SIGNAL & MODE OPERATION TOTAL KW BOARD ACTIONW1, W2 & Y/Y2AUX HEATON5 KWstage 1 Heat on

Pagina 26

709172C (Replaces 709172B)INSTALLATION / PERFORMANCE CHECK LISTINSTALLER NAME:CITY: STATE:INSTALLATION ADDRESS:CITY: STATE:unit model #unit serial #Mi

Pagina 27

4GENERAL INFORMATIONThis appliance has been tested for capacity and efficiency in accordance with AHRI Standards and will provide many years of safe an

Pagina 28

5• Before occupying the structure: The lter must bereplaced or cleaned, the duct work must be inspected and cleaned of any construction debr

Pagina 29

6AIR HANDLER INSTALLATIONThe B6 Series Air Handler is shipped ready for vertical upflow installation and is approved for attic, basement, alcove/closet

Pagina 30

7Horizontal InstallationsThe B6 Series air handler can be installed horizontally in an attic, basement, crawl space or alcove. It can also be suspende

Pagina 31

8 WARNING:The coil in the air handler is factory shipped with a nitrogen charge. Avoid direct face exposure or contact with valve when gas is escaping

Pagina 32 - PROPOSITION 65 WARNING:

9Connecting the LinesetsIMPORTANT NOTES FOR HORIZONTAL OR DOWNFLOW INSTALLATIONS WITH TXV VALVE:• Thesensingbulbmustbelocatedushagainstthes